Firmware for CMS2000 (Phoenixtec) solar invertor upgrade

With CMS in administration it is extremely difficult to find the latest firmware for CMS2000, I managed to find a copy from a Whirlpool forum member.

You can download it below;

CMS2000 Re Flash.rar

ModelParameter.zip

Below is an excerpt from the included procedure;

CMS 2000 Parameter Change.

  1. Apply DC supply only to the inverter. The unit will sit in ‘Grid Fault’ mode.

  2. Open Sunville Flash Tool ( or similar)

    image

  3. Click Setting & select your com port

    (if you do not know your com port settings. Contact your IT provider)

    image

  4. Click OK

  5. Click ‘load -> Open’ or click the folder icon to select the varied firmware version.

    image

  6. Select the file SV4KA.mot file

    image

  7. Click OK

  8. Click ‘flash’. If the correct coms port is selected the CMS 2000 will display FLASH. This process will take approx 2mins.

  9. Once the firmware is updated, you will get the following message, Click ‘OK’

    image

  10. Close the Flash Tool and open CMS ProControl. Select and enable the corresponding com port. (if you do not know your com port settings. Contact your IT provider)

    image

    image

  11. The serial number on the inverter will display.

    image

  12. Left click once to select the inverter. The bar at the top will go black.

    image

  13. Right click once and select parameter.

    image

  14. Password is: administrator

    The parameters will then be displayed.

    image

  15. Change the Vac-Max (V) to 270 volts, the highest permissible as per AS4777. Click Setting.

  16. Once your settings have changed. You will see the below message. Click OK

    image

  17. Disconnect the DC supply and allow the inverter to power down. Once discharged, turn on the DC and AC supply and connect to the grid. The current settings can be seen by double-clicking on the serial number in CMS ProControl.

    image

  18. Process Complete.

Model Parameters Error

Occasionally we have had the following error. If this occurs, you will not be able to change the parameter settings.

image

If this occurs, you can download the updated file from. http://carbonmanagement.com.au/support/ModelParameter.zip

Once this has been downloaded, you will need to extract the downloaded ModelParameter.txt file

& place it in c:\programfiles(x86)\CMS Pro Control & replace the existing file. Reopen CMS Pro Control & you should not see the error message.


Posted

in

by

Comments

6 responses to “Firmware for CMS2000 (Phoenixtec) solar invertor upgrade”

  1. Justin Avatar
    Justin

    Thanks for this helpful guide – the only place online where I have found this specific information that I needed to change the maximum AC voltage. (Our line voltage is quite high). One thing that I found though was that the password I needed was admin (not administrator). Not sure if that was the default or the default. Also, I had to use the a new version of the Pro Control that I found here:

    http://web.archive.org/web/20130410194800/http://solaraustralia.com.au/ProControlSetup2.5.2.1.exe

    As the version you had wouldn’t install in my version of Windows 7.

    Thanks

    1. MECTILE Avatar

      Justin, thanks for sharing.

  2. Ben McCall Avatar
    Ben McCall

    I am looking for a ink to the mentioned Flash tool
    Could not google search a copy – CMS, Sunville and Phoenixtec key words
    Can you supply a link please? Thank you

  3. gil Avatar
    gil

    hi,
    this procedure fix the eeprom error?
    i looking for a solution to fix this problem
    could you help me?
    thanks

  4. Rob Fincher Avatar
    Rob Fincher

    Hello t,
    Do you have any ideas on how to fix the EEPROM failure error on the CMS2000. Presumably you need software to access the EEPROM, although the problem could be component failure. And thanks for the info you’ve provided here – very much appreciated.

  5. SerGre Avatar
    SerGre

    Hi t,
    Have a cv10000, also called Sunville 10000 device from Phoenixtec, with EEPROM error. I search anywhere, no one seems to have this firmware. Where can i get this firmware for my device?
    How you get your file, did you contact Phoenixtec directly?
    Regards,
    SerGre

Leave a Reply

Your email address will not be published. Required fields are marked *